Mon – Fri: 8:00am – 5:00pm
(817) 416-2881

VRF Technology

WHAT IS VARIABLE REFRIGERANT FLOW?

Variable Refrigerant Flow, or VRF technology, is equipment that routes 2 and 3-pipe refrigerant circuits from one outdoor unit to multiple indoor units (or zones) and is capable of providing heating and cooling at the same time as different zones require.

Unlike traditional refrigerant systems that are either “on” and operating at 100% capacity or “off”, VRF equipment utilizes inverter compressors which provide variable speed operation. Why is this so important? Because your HVAC systems seldom need to provide 100% of the capacity they are designed for.

VRF systems routinely operate at partial loads in the range of 30 to 70% which provides more consistent indoor temperatures and humidity levels as well as provides energy efficiency.

Because of this part-load capability, VRF systems are as efficient, and often more efficient, than commercial chiller/boiler systems while at the same time offering much greater design flexibility and much more usable square footage. .

VRF VERSUS VRV VERSUS VRT

Daikin is an 80-year old company that is dedicated to manufacturing refrigerants and air conditioning equipment.  In recent years, they have purchased well known US based manufactures such as McQuay and Goodman and have become the largest manufacturer of air conditioning equipment worldwide.  In the 1980’s, when Daikin began selling this technology, Daikin used the acronym “VRV” meaning Variable Refrigerant Volume.
As other manufacturers such as Mitsubishi and LG developed competing products, they called it “VRF” (Variable Refrigerant Flow) and since the term “VRF” has become the more widely used term for this technology.
Encore Mechanical, LLC coined and describes the group, including all manufacturers of Variable Refrigerant systems as “VRT” meaning Variable Refrigerant Technologies.

VRT ADVANTAGES

  • Very efficient –similar or better than chillers, 180% as efficient as standard splits and RTU’s
  • Small space requirements = more net rentable SF.
  • Individual room control – indoor fan coils range from ½-ton up to 8-ton and can heat and cool independently.
  • Power distribution – allows building owners to proportion electrical consumption between tenants and bill via automated electronic means.
  • Remote control and monitoring via internet.
  • Durability – VRF gained a lot of ground in Japan and the Caribbean 25 years ago because they were designed for use where saltwater air corrosion and hurricanes are common.
  • Durability – these systems have been outlasting chiller plants.
  • Excellent dehumidification – which is great for building preservation.
  • Design flexibility – wall mounted, ceiling mounted, concealed non-ducted cassettes fit within acoustical ceiling tiles, and concealed ducted indoor unit types up to 8-ton units.
  • Very low maintenance (particularly compared to central plants).
  • Modular installation: these systems are great for retrofits, “add-on” tonnage, and phased construction.
  • No gas required; all electric.  No auxiliary heat strips needed.
  • Suitable for a broad geographical range.  These systems perform to subzero temperatures.

WHY CONTRACTOR SELECTION IS IMPORTANT

  • The most pronounced disadvantage to VRF technology is that the manufacturer’s do no limit unqualified mechanical contractors from purchasing these systems.  To get the efficiency, durability, and superior control these systems provide, the piping systems and control systems must be installed per the manufacturers’ very specific instructions.
    Purchasers of VRF installations should qualify their installers by requiring all of the following:
    • Field Supervisors shall have attended the manufacturer’s classes totaling 4 days.  Each manufacturer varies, but generally supervisors shall have completed the “2-day Installation” class and an additional 2-day class titled “Commissioning” or “Service” depending on the manufacturer.  Plus references for three previous installations.
    • All field personnel handling any part of the refrigerant piping system, control wiring, or actual equipment shall have completed at least the “2-day Installation” class offered by the manufacturer prior to commencement.
    • All mechanical contractors submitting proposals for the work shall substantiate their VRF experience detailing the scope, type of system (heat pump or heat recovery), tonnage, and provide references for the work.
    • All piping shall be brazed only when flowing nitrogen and flared with manufacturer recommended tools.  All piping shall be pressure tested to manufacturer guidelines.  All refrigerant piping systems shall be vacuumed to below 500 microns and observed by owner’s appointed representative prior to adding of “trim” refrigerant and commissioning (start-up).
    Start-up and commissioning shall be performed only by a manufacturer certified commissioning agent which may be a qualified contractor, manufacturer’s representative, or manufacturer’s employee.  VRF manufacturers limit and void their warranties on systems not properly installed and commissioned.

ENCORE MECHANICAL CORE COMPETENCIES

VRF-Technologies
VARIABLE REFRIGERANT TECHNOLOGIES
VRF-Service
VRF SERVICE
Multifamily-VRF
MULTIFAMILY VRF
VRF-Consulting
VRF CONSULTING